Voltage Drop Calculator

Calculate voltage drop in a copper or aluminium cable run for single-phase/DC or three-phase circuits.

Voltage drop
6.451 V
Drop %
2.8%
Voltage at load
223.55 V

Step-by-step working

  1. R (one conductor) = ρL/A = 1.68e-8 × 30 / 2.5e-6 = 0.2016 Ω
  2. Vd = 2 × I × R = 6.451 V

Mathematical Formula

R = ρ L / A (one conductor). Single-phase/DC: Vd = 2 I R. Three-phase: Vd = √3 I R. Drop % = Vd / V × 100. (Resistive only, 20 °C.)

Overview & Explanation

Current flowing through cable resistance loses voltage. Long runs and small conductors increase the drop.

How It Works

  • Compute one-conductor resistance from resistivity.
  • Multiply by 2 (go-and-return) or √3 (three-phase).
  • Compare with the supply voltage.

Practical Applications

  • Sizing cables for pumps, EV chargers, solar.
  • Checking long garden or farm runs.

Example 1: 30 m, 16 A, 2.5 mm² Cu, 230 V

Domestic circuit.

1

Inputs

One-way cable length (m): 30 · Load current (A): 16 · Conductor cross-section (mm²): 2.5 · Conductor: Copper (ρ = 1.68×10⁻⁸ Ω·m) · System: Single-phase / DC (2 wires) · Supply voltage (V): 230

= entered
2

Step 1

R (one conductor) = ρL/A = 1.68e-8 × 30 / 2.5e-6 = 0.2016 Ω

3

Step 2

Vd = 2 × I × R = 6.451 V

4

Voltage drop

Result

= 6.451 V

Example 2: 100 m, 40 A, 16 mm² Al, 415 V 3-phase

Feeder.

1

Inputs

One-way cable length (m): 100 · Load current (A): 40 · Conductor cross-section (mm²): 16 · Conductor: Aluminium (ρ = 2.65×10⁻⁸ Ω·m) · System: Three-phase (balanced) · Supply voltage (V): 415

= entered
2

Step 1

R (one conductor) = ρL/A = 2.65e-8 × 100 / 16e-6 = 0.16563 Ω

3

Step 2

Vd = √3 × I × R = 11.475 V

4

Voltage drop

Result

= 11.475 V

How it's calculated & sources

R = ρ L / A (one conductor). Single-phase/DC: Vd = 2 I R. Three-phase: Vd = √3 I R. Drop % = Vd / V × 100. (Resistive only, 20 °C.)

Frequently Asked Questions

What drop is acceptable?
Many codes recommend ≤ 3% for branch circuits and ≤ 5% total; check IS 732 / IEC 60364 / NEC as applicable.
Does temperature matter?
Yes, resistance rises about 0.4% per °C for copper; this uses 20 °C values.
Why not include reactance?
For small cables reactance is negligible; large feeders need impedance tables.